Greenhouse Heating Calculator

Enter the greenhouse area and target temperatures to size your heater.

How it is calculated

The tool follows the NGMA Heat Loss Guideline. Loss through the covering is U × C × W × A × ΔT: U from the guideline's Table 1 for the covering you pick (single glass 1.13, double glazing 0.70, single film plastic 1.20, inflated double film 0.70, single film over glass 0.85, double film over glass 0.60, corrugated FRP 1.20, structured plastic sheet 0.58 at 16 mm, 0.65 at 8 mm, 0.72 at 6 mm), C the construction factor from Table 2 (metal frame and glazing bars at 16 to 24 inches 1.08, fiberglass on metal 1.03, film on metal 1.02, film or fiberglass on wood 1.00), W the wind factor from Table 3 (1.00 at 15 mph rising by 0.04 per 5 mph to 1.16 at 35 mph), A the covering area in sq ft and ΔT = inside − outside in °F. Air leakage adds 0.018 × N × V × ΔT, with N air changes per hour (Table 4: 0.6 to 1.0 for plastic film, 1.0 for sealed glass or structured sheet, 1.25 for unsealed lapped glass, 0.9 for film over glass, 1.5 for an old house in good repair, 2 to 4 in poor repair) and V the inside volume in cu ft. Leave the volume blank and only the covering loss is shown, with a note.

Watts are BTU/hr ÷ 3.412. Choosing Metric under Units takes m², m³ and °C (a difference in °C is 1.8 times as many °F) and shows kW and watts. A link without covering, frame or wind uses single glass, a metal frame with 16 to 24 inch glazing bars and 15 mph. If the inside temperature is not higher than the outside one, or the area is zero or negative, there is no result. The guideline's U values are recommended values; for a specific material use the manufacturer's figure, and the guideline makes no reduction for heat curtains.

Worked example

A greenhouse has 600 sq ft of inflated double film on a metal frame, 1,500 cu ft inside, in a place where design winds reach 25 mph. You want 65 °F inside when it falls to 20 °F outside, so ΔT = 45 °F. Through the covering: 0.70 × 1.02 × 1.08 × 600 × 45 = 20,820 BTU/hr. Air leakage at 0.8 air changes an hour: 0.018 × 0.8 × 1,500 × 45 = 972 BTU/hr. The tool shows 21,792 BTU/hr, about 6,387 W. The same house in single film (U 1.20) would need 35,692 + 972 = 36,664 BTU/hr.

Try this example →

Common mistakes

  • Entering the floor area instead of the surface area of the walls and roof. The loss happens through the covering, so floor area usually underestimates it.
  • Typing temperatures in °C with Units set to US. The US mode works in °F, so 20 °C must be entered as 68 °F; or choose Metric to enter °C.
  • Using the average winter temperature as the outside value. Size for the coldest night you expect, not the typical one.
  • Using square meters with Units set to US. In US units the area field is in square feet; multiply square meters by 10.764 first, or choose Metric.
  • Putting the target below the outside temperature, which means cooling. The tool then gives no result.
  • Leaving the volume blank. Without it the air leakage is left out, and in an old, leaky house that can be a large part of the load.

Sources

About this calculator

Sizing a greenhouse heater starts with the heat that escapes on the coldest night. This calculator follows the National Greenhouse Manufacturers Association's Heat Loss Guideline: the loss through the covering is U × A × ΔT, where U depends on the covering (1.13 for single glass, 1.20 for single film plastic, 0.70 for inflated double film or double glazing, 0.58 to 0.72 for structured plastic sheet, in BTU/hr per sq ft per °F), A is the surface area and ΔT the difference between the inside and outside design temperatures. That is multiplied by a construction factor for the frame (1.00 to 1.08) and, where design winds exceed 15 mph, a wind factor (up to 1.16 at 35 mph). Air leaking in adds 0.018 × N × V × ΔT, with N air changes per hour and V the inside volume in cubic feet. The result is the heater output, in BTU/hr and watts (kW in metric).

This method is used by gardeners, greenhouse growers, and hobbyist horticulturists deciding what size heater to buy before winter — undersizing leaves plants exposed to frost during cold snaps, while oversizing wastes money on both the unit and its running cost. The guideline says its U values are recommended values and the manufacturer should be consulted for specific materials; walls of a different material (concrete, block) are best worked out separately.

Was this helpful?

You can pick up to 3 reactions.

Note from the editors

The outside temperature moves the answer most, and the covering next. With 500 sq ft of single glass on a metal frame and 60 °F inside, planning for 20 °F outside gives 24,408 BTU/hr through the covering, and for 0 °F, 36,612; inflated double film instead of single glass takes about 38 percent off. Add the inside volume so air leakage is counted too. What is the coldest night your greenhouse has had to get through?

Comments

  • Be the first to comment.