Generator Fuel Consumption Calculator

Estimate the fuel a generator burns over a run, from its full-load rate in liters or US gallons per hour.

How it is calculated

Inputs: Full-load consumption is the fuel the generator burns per hour at 100% load (from the data plate or manual, in liters or US gallons per hour: pick the unit in Fuel unit), load is the average load in percent, and hours is the run time.

fuel per hour = full-load consumption × (i + (1 − i) × load ÷ 100), with i the no-load share
total fuel = fuel per hour × hours

This is the straight-line fuel curve the HOMER Pro manual describes: an intercept, the “no-load fuel consumption” a generator burns while idling, plus a slope proportional to the output. HOMER takes the intercept from the generator's own fuel data, so the tool asks for the no-load share i as a percentage of the full-load burn. Real engines do not follow this exactly, so treat the answer as an estimate. Full-load rate and hours must be above zero. Load may be 0 (pure idle burn) up to 100, and the no-load share 0 to 100%; a load above 100 or below 0 gives no result. Results are shown to two decimals, in the unit of the full-load figure.

Worked example

A generator burns 3.2 L/h at full load. It will run for 8 hours at an average load of 50%. With a no-load share of 25%, fuel per hour is 3.2 × (0.25 + 0.75 × 0.50) = 3.2 × 0.625 = 2.00 L. Total: 2.00 × 8 = 16.00 L for the shift. A tank of 20 L would therefore cover it with a small reserve. If the generator's fuel table shows 0.5 L/h at no load, that is 0.5 ÷ 3.2 = 16%, and the shift needs 3.2 × (0.16 + 0.84 × 0.5) × 8 ≈ 14.8 L instead.

Try this example →

Common mistakes

  • Entering the generator's rated power in kW instead of its full-load fuel use per hour. The first field is a fuel rate, not output.
  • Typing the load as a fraction (0.5) instead of a percentage (50), which is read as a load of half a percent and gives almost the idle burn.
  • Using the peak load (the moment the biggest appliance starts) rather than the average load over the run. That overstates the fuel.
  • Entering the per-hour rate as a per-day or per-tank figure; the field is a rate per hour.
  • Expecting half the load to use half the fuel. With the idle allowance, 50% load gives 62.5% of the full-load burn, and even 0% load still burns the no-load share.

Sources

About this calculator

A generator's fuel consumption rating is usually quoted at full load — the number of liters or gallons of diesel or gasoline it burns per hour when producing its rated kilowatt output. Actual burn rate falls as the load percentage drops, but never to zero, because an engine still needs fuel to idle its cylinders and alternator even with almost no electrical demand. This calculator uses the straight-line fuel curve of the HOMER Pro manual: a no-load burn, which you enter as a share of the full-load figure from your generator's data (25% by default), plus the rest in direct proportion to the load percentage (burn = full-load burn × (i + (1 − i) × load/100)), then multiplies by the run time to give a practical estimate of total fuel used, in liters or US gallons.

Electricians, event planners and site managers use this kind of estimate to size a fuel tank for a job, budget diesel costs for a multi-day power outage, or work out how often a portable generator needs refueling during a camping trip or construction shift. Knowing expected consumption also helps decide whether a smaller, more efficient unit running near its sweet-spot load would be cheaper to run than an oversized generator idling at low load.

A generator rated in US gallons per hour can be entered as it is: choose US gallons and the results come out in gallons. A load of 0% returns the no-load burn.