Aquarium Chiller Sizing Calculator

Size an aquarium chiller from your tank volume and the temperature drop you need.

How it is calculated

The tool treats the tank as a body of water and works out the heat that has to be removed. Water weighs about 8.34 lb per US gallon and needs 1 BTU to change one pound by 1 °F, so: BTU total = gallons × 8.34 × temperature drop (°F). The capacity is then BTU/hr = BTU total ÷ hours. Watts are BTU/hr × 0.29307107, and the nominal HP figure is BTU/hr ÷ 12,000, the trade rule of thumb that one ton of cooling is about one compressor horsepower. It is not mechanical horsepower (2,545 BTU/hr), so compare chillers by their rated BTU/hr. All three inputs must be above zero, otherwise no result is shown. Volume is in US gallons and the drop in °F, or, with the unit system set to metric, liters and °C: the tool then converts them (liters ÷ 3.785411784, a °C drop × 1.8, since a temperature difference has no 32 offset) and runs the same formula, which is 4.184 kJ per liter per °C, so the same tank gives the same BTU/hr, watts and HP in both systems. The capacity stays in BTU/hr in metric too, the unit chillers and air conditioners are sold by, with watts beside it. Hours is the time you allow for the pull-down. The result is the pull-down capacity only: it does not add the steady heat load from lights, pumps or the room, which in a warm room often decides the size, so it is a lower bound, not a chiller rating.

Worked example

A 75-gallon tank must be cooled by 8 °F in 6 hours. Heat to remove: 75 × 8.34 = 625.5 lb of water per degree, times 8 °F = 5,004.00 BTU in total. Spread over 6 hours that is 5,004 ÷ 6 = 834.00 BTU/hr. In watts, 834 × 0.29307107 = 244.42 W, and 834 ÷ 12,000 = 0.070 nominal HP. That 834.00 BTU/hr is the pull-down share only: the chiller must also carry the heat that keeps flowing in from the room, lights and pumps, which the tool leaves out, so a real unit has to be rated well above it.

Try this example →

Common mistakes

  • Entering a °C drop while the unit system is on US units. The field then expects Fahrenheit degrees, so an 8 °C drop typed as 8 needs almost twice the capacity shown (8 °C is 14.4 °F); switch the unit system to metric instead.
  • Typing the tank size in liters while the unit system is on US units. Volume is then in US gallons (1 gallon is about 3.785 liters), so 300 liters is roughly 79 gallons.
  • Entering the target temperature instead of the drop. If the tank is at 82 °F and you want 78 °F, the drop is 4, not 78.
  • Using the full tank size when a sump, rock and substrate take up space. Use the real water volume, not the glass dimensions.
  • Setting a very short pull-down time. Halving the hours doubles the BTU/hr; a longer period gives a much smaller, cheaper chiller.

Sources

Based on a common rule of thumb; no published standard was found.

About this calculator

Aquarium chiller sizing calculates the cooling capacity in BTU/hr needed to lower a tank's water temperature by a specific number of degrees, based on the tank's water volume (in US gallons, or liters with the unit system set to metric), the desired temperature drop (in °F, or °C in metric), and how quickly the chiller needs to achieve it. Larger volumes and bigger temperature drops both require proportionally more cooling capacity. Ambient room temperature and tank insulation are not part of the calculation, even though heat constantly migrates back into the tank from the surrounding air, so a warm room calls for a chiller sized above the result.

Reef keepers and tropical/coldwater fish keepers size a chiller carefully because many sensitive species — particularly corals and coldwater fish like goldfish or certain trout — suffer stress or death outside a narrow temperature band, and an undersized chiller can run constantly without ever reaching the target temperature during hot weather, while lighting and pump equipment in the tank add heat load that the calculator does not include, so leave some headroom for it.

Tank volume, how many degrees you need to drop and how many hours you allow for it set the heat to remove; you get that total in BTU and the pull-down capacity in BTU/hr, watts and nominal horsepower. That is a lower bound for the chiller, not its rating: the steady heat load from the room, lights and pumps comes on top.